| pH | 6.1 | - | Context only — no numeric pass/failNo health-based guideline. Optimum operational pH varies with water and materials, usually 6.5–8.5; chlorine disinfection preferably below pH 8. These are process conditions, not raw-water pass/fail limits.Source · PDF page 274 | Context onlyNo health-based guideline. Optimum operational pH varies with water and materials, usually 6.5–8.5; chlorine disinfection preferably below pH 8. These are process conditions, not raw-water pass/fail limits. |
|---|
| Colour | 1 | True colour units | Context only — no standalone numeric pass/failNo health-based guideline. Colour below 15 true colour units (TCU) is usually acceptable; reporting scale must be confirmed.Source · PDF page 271 | Context onlyNo health-based guideline. Colour below 15 true colour units (TCU) is usually acceptable; reporting scale must be confirmed. |
|---|
| Turbidity | 2.70 | NTU | Context only — no numeric pass/failOperational target, not a raw-water health limit. WHO describes large supplies achieving 0.5 NTU before disinfection at all times and an average of 0.2 NTU or less; small-supply feasibility differs.Source · PDF page 275 | Context onlyOperational target, not a raw-water health limit. WHO describes large supplies achieving 0.5 NTU before disinfection at all times and an average of 0.2 NTU or less; small-supply feasibility differs. |
|---|
| Electrical conductivity (CND) | 693 | µS/cm | Context only — no numeric pass/failNo WHO numeric drinking-water guideline used here. It describes ionic conductivity, not drinking-water safety.Source · PDF page 90 | Context onlyNo WHO numeric drinking-water guideline used here. It describes ionic conductivity, not drinking-water safety. |
|---|
| Total dissolved solids (TDS) | 324 | mg/l | Context only — no numeric pass/failNo health-based guideline. WHO describes palatability as generally good below about 600 mg/L and increasingly poor above about 1000 mg/L.Source · PDF page 275 | Generally good palatabilityPalatability screening only, not a health-based pass/fail. The 600–1000 mg/L review band is a GlobalUF display grouping. TDS alone does not establish drinking-water safety. |
|---|
| Total hardness (CaCO3) | 173 | mg/l | Context only — no numeric pass/failNo health-based guideline. Assess scaling and treatment requirements for the intended use.Source · PDF page 272 | Context onlyNo health-based guideline. Assess scaling and treatment requirements for the intended use. |
|---|
| Magnesium (Mg) | 17 | mg/l | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Chloride (Cl2) | 7.2 | mg/l | Context only — no numeric pass/failNo health-based guideline. Taste becomes more noticeable above about 250 mg/L.Source · PDF page 270 | Context onlyNo health-based guideline. Taste becomes more noticeable above about 250 mg/L. |
|---|
| Sulfates (SO4) | 2 | mg/l | Context only — no numeric pass/failNo health-based guideline. Taste depends on the associated cation.Source · PDF page 275 | Context onlyNo health-based guideline. Taste depends on the associated cation. |
|---|
| Fluoride (F) | 0.5 | mg/l | 1.5 mg/LConsider total intake and water consumption when setting national standards.Source · PDF page 581 | At or below referenceCompared on the reported analytical basis. |
|---|
| Nitrates (N-NO3) | 2 | mg/l | 50 mg/L as NO3 ionAs NO3 ion. Also assess nitrate/50 + nitrite/3 <= 1, both as ions in mg/L.Source · PDF page 582 | At or below referenceCalculated as NO3 from the reported nitrogen basis. Comparison value: 8.85714 mg/L. |
|---|
| Nitrites (NO2) | <0.01 | mg/l | 3 mg/L as NO2 ionAs NO2 ion. Also assess nitrate/50 + nitrite/3 <= 1, both as ions in mg/L.Source · PDF page 582 | Reported bound below referenceCompared on the reported analytical basis. |
|---|
| Ammonium (NH4) | <0.01 | mg/l | Context only — no numeric pass/failNo health-based guideline. It can be relevant to treatment and disinfection.Source · PDF page 270 | Context onlyNo health-based guideline. It can be relevant to treatment and disinfection. |
|---|
| Iron (Fe) | 0.13 | mg/l | Context only — no numeric pass/failNo health-based guideline; taste, colour and deposits can affect acceptability.Source · PDF page 273 | Context onlyNo health-based guideline; taste, colour and deposits can affect acceptability. |
|---|
| Manganese (Mn) | 0.07 | mg/l | 0.08 mg/L (provisional)Total manganese; aesthetic concerns also apply. Provisional guideline; flags P.Source · PDF page 582 | At or below referenceCompared on the reported analytical basis. |
|---|
| Arsenic (As) | <0.01 | µg/l | 0.01 mg/L (provisional)Health-based guideline; consult the chemical fact sheet for application. Provisional guideline; flags A,T.Source · PDF page 580 | Reported bound below referenceCompared on the reported analytical basis. |
|---|
| Lead | 0.001 | mg/l | 0.01 mg/L (provisional)Health-based guideline; consult the chemical fact sheet for application. Provisional guideline; flags A,T.Source · PDF page 582 | At or below referenceCompared on the reported analytical basis. |
|---|
| Cadmium | <2 | µg/l | 0.003 mg/LHealth-based guideline; consult the chemical fact sheet for application.Source · PDF page 580 | Reported bound below referenceCompared on the reported analytical basis. |
|---|
| Ambient temperature | 27.2 | °C | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Cyanide | 0.001 | mg/l | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Odour | 0 | - | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Sample temperature | 28.2 | °C | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Taste | 0 | - | Not configured | Not assessedNo matching reference configured; do not infer that WHO has no guidance. |
|---|
| Faecal coliforms | 0 | CFU/100mL | Not detectable in 100 mLWHO 2026, Table 7.10; criterion for water intended for drinking.Source · PDF page 190 | Not detected in reported testApplies only to this test and sample; not proof of overall drinking-water safety. |
|---|