Back to Water Map

China Tanjiang River water sample CN-05

River water analysis for this sample, with English reporting and a WHO drinking-water reference comparison.

Sample evidence summary

CN-05 documents a river source in Tanjiang River / Yinzhou Lake, Shuangshui, Xinhui, Jiangmen, Guangdong, China. The reported source is Customer-supplied historical water-analysis table. Use the selected measurements below alongside the complete results table and the source limitations when defining project requirements.

CN-05 records river water results for Tanjiang River / Yinzhou Lake, Shuangshui, Xinhui, Jiangmen, Guangdong, China. Source: Customer-supplied historical water-analysis table.

  • pH: 7.44 Not specified in source (as reported).
  • Turbidity: 6.7 NTU (as reported).
  • Total dissolved solids: 1510 mg/L (as reported).
  • Fluoride: 0.3 mg/L (as reported).
  • Nitrate (as NO3 ion): 6.98 mg/L (as reported).

This summary reproduces selected reported results; it is not a complete drinking-water safety assessment. Dates and reporting limitations are shown below.

Explore water reports from China

Country
China
Area
Tanjiang River / Yinzhou Lake, Shuangshui, Xinhui, Jiangmen, Guangdong
Water source
River water
Sample ID
CN-05
Sampling date / period
Date needs verification
Report date
Not supplied
Source
Customer-supplied historical water-analysis table
Version
1

Results and WHO comparison

Analysis results for sample CN-05
ParameterReported resultUnitWHO referenceComparison
pH7.44Not specified in sourceContext only — no numeric pass/failNo health-based guideline. Optimum operational pH varies with water and materials, usually 6.5–8.5; chlorine disinfection preferably below pH 8. These are process conditions, not raw-water pass/fail limits.Source · PDF page 274Context onlyNo health-based guideline. Optimum operational pH varies with water and materials, usually 6.5–8.5; chlorine disinfection preferably below pH 8. These are process conditions, not raw-water pass/fail limits.
Turbidity6.7NTUContext only — no numeric pass/failOperational target, not a raw-water health limit. WHO describes large supplies achieving 0.5 NTU before disinfection at all times and an average of 0.2 NTU or less; small-supply feasibility differs.Source · PDF page 275Context onlyOperational target, not a raw-water health limit. WHO describes large supplies achieving 0.5 NTU before disinfection at all times and an average of 0.2 NTU or less; small-supply feasibility differs.
Electrical conductivity at 25°C2768μS/cmContext only — no numeric pass/failNo WHO numeric drinking-water guideline used here. It describes ionic conductivity, not drinking-water safety.Source · PDF page 90Context onlyNo WHO numeric drinking-water guideline used here. It describes ionic conductivity, not drinking-water safety.
Total dissolved solids1510mg/LContext only — no numeric pass/failNo health-based guideline. WHO describes palatability as generally good below about 600 mg/L and increasingly poor above about 1000 mg/L.Source · PDF page 275Poor palatability — evaluate salt reductionPalatability screening only, not a health-based pass/fail. The 600–1000 mg/L review band is a GlobalUF display grouping. TDS alone does not establish drinking-water safety.
Total solids1751mg/LContext only — no standalone numeric pass/failNo numeric WHO drinking-water guideline is used in this library; distinguish dissolved and suspended solids.Source · PDF page 275Context onlyNo numeric WHO drinking-water guideline is used in this library; distinguish dissolved and suspended solids.
Carbonate hardness1.46mmol/LContext only — no numeric pass/failNo health-based guideline. Assess scaling and treatment requirements for the intended use.Source · PDF page 272Context onlyNo health-based guideline. Assess scaling and treatment requirements for the intended use.
Negative hardness (as reported)0mmol/LContext only — no numeric pass/failNo health-based guideline. Assess scaling and treatment requirements for the intended use.Source · PDF page 272Context onlyNo health-based guideline. Assess scaling and treatment requirements for the intended use.
Non-carbonate hardness2.02mmol/LContext only — no numeric pass/failNo health-based guideline. Assess scaling and treatment requirements for the intended use.Source · PDF page 272Context onlyNo health-based guideline. Assess scaling and treatment requirements for the intended use.
Total hardness3.48mmol/LContext only — no numeric pass/failNo health-based guideline. Assess scaling and treatment requirements for the intended use.Source · PDF page 272Context onlyNo health-based guideline. Assess scaling and treatment requirements for the intended use.
Phenolphthalein alkalinity0mmol/LContext only — no standalone numeric pass/failNo numeric WHO drinking-water guideline is used in this library. Assess buffering, pH and scaling in process design.Source · PDF page 274Context onlyNo numeric WHO drinking-water guideline is used in this library. Assess buffering, pH and scaling in process design.
Total alkalinity (methyl orange)1.46mmol/LContext only — no standalone numeric pass/failNo numeric WHO drinking-water guideline is used in this library. Assess buffering, pH and scaling in process design.Source · PDF page 274Context onlyNo numeric WHO drinking-water guideline is used in this library. Assess buffering, pH and scaling in process design.
Calcium46.98mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Magnesium53.91mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Sodium414.43mg/LContext only — no numeric pass/failNo health-based guideline. The average taste threshold is about 200 mg/L.Source · PDF page 274Context onlyNo health-based guideline. The average taste threshold is about 200 mg/L.
Potassium18.76mg/LContext only — no numeric pass/failNo health-based guideline established.Source · PDF page 579Context onlyNo health-based guideline established.
Bicarbonate88.85mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Carbonate0mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Chloride738.686mg/LContext only — no numeric pass/failNo health-based guideline. Taste becomes more noticeable above about 250 mg/L.Source · PDF page 270Context onlyNo health-based guideline. Taste becomes more noticeable above about 250 mg/L.
Sulfate107.64mg/LContext only — no numeric pass/failNo health-based guideline. Taste depends on the associated cation.Source · PDF page 275Context onlyNo health-based guideline. Taste depends on the associated cation.
Fluoride0.3mg/L1.5 mg/LConsider total intake and water consumption when setting national standards.Source · PDF page 581At or below referenceCompared on the reported analytical basis.
Nitrate (as NO3 ion)6.98mg/L50 mg/L as NO3 ionAs NO3 ion. Also assess nitrate/50 + nitrite/3 <= 1, both as ions in mg/L.Source · PDF page 582At or below referenceCompared on the reported analytical basis.
Nitrite (as NO2 ion)<0.10mg/L3 mg/L as NO2 ionAs NO2 ion. Also assess nitrate/50 + nitrite/3 <= 1, both as ions in mg/L.Source · PDF page 582Reported bound below referenceCompared on the reported analytical basis.
Ammonia nitrogen0.01mg/LContext only — no numeric pass/failNo health-based guideline. It can be relevant to treatment and disinfection.Source · PDF page 270Context onlyNo health-based guideline. It can be relevant to treatment and disinfection.
Ammonium (reported as ammonia ion)<0.10mg/LContext only — no numeric pass/failNo health-based guideline. It can be relevant to treatment and disinfection.Source · PDF page 270Context onlyNo health-based guideline. It can be relevant to treatment and disinfection.
Total iron<0.01mg/LContext only — no numeric pass/failNo health-based guideline; taste, colour and deposits can affect acceptability.Source · PDF page 273Context onlyNo health-based guideline; taste, colour and deposits can affect acceptability.
Total aluminiumNot testedmg/LContext only — no numeric pass/failNo guideline value. Coagulation-process optimization levels are not raw-water safety limits.Source · PDF page 270Context onlyNo guideline value. Coagulation-process optimization levels are not raw-water safety limits.
Barium*Not testedmg/L1.3 mg/LHealth-based guideline; consult the chemical fact sheet for application.Source · PDF page 580Not assessedNo unambiguous numeric result or detection limit is available.
BOD5*6.7mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Chemical oxygen demand (permanganate method)1.42mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Free carbon dioxide6mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Hydroxide0mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Non-reactive silica2.9mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Phosphate<0.10mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Reactive silica2.98mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Strontium*Not testedmg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Total organic carbon*1.73mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Total silica5.88mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.
Total suspended solids241mg/LNot configuredNot assessedNo matching reference configured; do not infer that WHO has no guidance.

SAMPLE CN-05 · REFERENCE SCREENING

What these results indicate

0 above reference / detected3 at or below reference / not detected16 not assessed19 context only

No exceedance was identified among the results that could be compared. This does not establish that the water meets all WHO guidance: unassessed results, missing tests and source conditions remain relevant.

Nitrate and nitrite together: the combined WHO ratio also needs checking. Two exact results on compatible analytical bases were not available for that calculation.

Microbial evidence gap: this record has no separately identified E. coli or thermotolerant/faecal coliform result. Total coliforms and general bacterial counts do not replace that test.

Unresolved comparisons: review the reasons beside each result. ND/BLQ without a numeric limit, ambiguous units and unspecified chemical forms are not counted as compliant results.

Treatment options for this sample

Evaluate reverse osmosis for dissolved-salt reduction

Trigger: Total dissolved solids = 1510 mg/L; screening level > 1000 mg/L.

If the intended product-water specification requires lower salinity, evaluate BWRO with feed salinity, ionic composition, scaling potential and recovery. UF alone does not remove dissolved salts. Estuary or highly saline feeds may need a seawater-rated design.

GlobalUF screening trigger informed by WHO taste guidance; not a WHO health limit.

Explore Brackish Water Reverse Osmosis (BWRO) →

Evaluate clarification and ultrafiltration

Trigger: Turbidity = 6.7 NTU; screening level > 1 NTU.

Review coagulation/flocculation and sedimentation for elevated or variable solids, followed by filtration or UF where appropriate. Confirm seasonal peaks, particle characteristics and organic matter; use jar or pilot tests to select pretreatment. Include a suitable disinfection barrier for drinking-water use.

GlobalUF raw-water screening trigger (>1 NTU); WHO treatment/disinfection turbidity guidance is context-dependent, not a raw-water health limit.

Explore Ultrafiltration membranes →

Automatically generated screening from this sample record and the cited reference set. This is not an engineer-approved design, a national compliance certificate or a declaration that untreated water is safe to drink.

Source and interpretation

Table 2.7-2 in a historical technical specification. Date reproduced from the table column; sampling versus testing date is not specified. Laboratory and issue date are not supplied. Original values, blanks and not-tested entries are preserved; asterisks are unexplained in the excerpt. Results do not represent present-day conditions.

This is a sample record, not a treatment specification. A process design needs a current, representative source-water analysis and the intended product-water requirements.

WHO drinking-water guidance is used for screening, not certification of untreated source water. TDS categories describe palatability, not overall drinking-water safety. Original dates and laboratory details remain in the source archive.

Download WHO Drinking-water Quality Guidelines (2026 PDF)WHO source document · PDF · approximately 6 MB

FROM WATER ANALYSIS TO PROJECT REQUIREMENTS

Discuss your water quality with our engineering team

Tell us about your source water, required capacity and intended use. Our team can help review the data and define the next engineering steps.

Consult our engineering team
Email Icon Phone Icon WhatsApp Icon Messenger Icon